| パラメータ | 価値 |
|---|---|
| 18 V DC ... 30 V DC | |
| ヒューズ | electronic |
| 注記 | Interference emission |
| タイプ | Male |
| 色 | gray (RAL 7042) |
| 深さ | 52 mm |
| 幅 | 12.3 mm |
| 身長 | 45 mm |
| 一般的な | When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).Special precautionary measures must be taken in systems or machines, to prevent components from restarting (e.g., use of a safety PLC).Parallel connection of multiple circuit breakers is not permitted. |
| 製品タイプ | Device circuit breakers |
| 電圧降下 | 130 mV (at IN) |
| 湿度テスト | 96 h, 95 % RH, 40 °C |
| 取り付けタイプ | on base element |
| シャットダウン時間 | 130 ms (see time/current characteristic curve) |
| 識別 | UL Listed UL 508 |
| 製品ファミリー | CB E |
| チャンネル数 | 1 |
| スイッチオン遅延 | typ. 2 ms |
| トリッピング法 | E (electronic) |
| 記事の改訂 | 03 |
| 汚染度 | 2 |
| 接続方法 | pluggable |
| フェイルセーフ要素 | 10 A DC |
| 動作電圧 | 24 V DC |
| 消費電力 | 1.19 W (Nominal operation) |
| 公称電流IN | 6 A |
| 絶縁強度 | max. 30 V DC (Load circuit) |
| 寸法図 | |
| ポジション数 | 1 |
| 定格サージ電圧 | 0.5 kV |
| 保護の程度 | IP30 (Actuation area) |
| 最大容量負荷 | 20000 µF |
| 必要なバックアップヒューズ | not required, integrated failsafe element |
| 標準指定 | EMV |
| 温度ディレーティング | 5 A (at 50 °C) |
| 完全なモジュールの深さ | 77.3 mm |
| モジュール全体の幅 | 12.3 mm |
| 振動(操作) | 3g (according to IEC 60068-2-6, Test Fc) |
| モジュール全体の高さ | 90 mm |
| 接点接続タイプ | floating signal contact |
| 低電圧スイッチオフ | < 14 V (typ. OFF) |
| 規格/仕様 | EN 61000-6-3 |
| アクティブ電流制限 | typ. 1.25 x IN |
| 閉回路電流 I0 | typ. 8 mA (When switched on) |
| MTBF(IEC 61709、SN 29500) | 8320000 h (at 25 °C with 80 % load) |
| 最大動作電流 Imax | 0.5 A |
| 最小動作電流Imin | 10 mA |
| 周囲温度(動作) | -25 °C ... 50 °C (non-condensing) |
| 最大動作電圧UmaxDC | 30 V DC |
| 最小動作電圧 UminDC | 10 V DC |
| UL 94準拠の難燃性評価 | V-0 |
| 周囲温度(保管/輸送) | -40 °C ... 70 °C |