| パラメータ | 価値 |
|---|---|
| アイテム | Specifications |
| 重さ | Net weight: 75 g approx.Gross weight: 120 g approx. |
| 詳細 | Communication unit for DeviceNet |
| 製品 | Commnunication Unit for Open Network |
| 材料 | Enclosure: Polycarbonate |
| 部品番号 | SC-GU3-02 |
| 製品名 | Communication Unit for Open Network SC-GU3 |
| 製品番号 | SC-GU3-02 |
| 供給電圧 | 11 to 25 V DC Ripple P-P 10 % or less |
| アドレス設定 | 0 to 63 (64 or more: Error) |
| 周囲の湿度 | 35 to 85 % RH, Storage: 35 to 85 % RH |
| 周囲温度 | –10 to +55 ℃+14 to +131 ℉(No dew ondensation or icing allowed),(If 4 to 7 units are connected in cascade: –10 to +50 ℃+14 to +122 ℉,if 8 to 16 units are connected in cascade: –10 to +45 ℃+14 to +113 ℉)Storage: –20 to +70 ℃–4 to +158 ℉ |
| 通信ケーブル | Complies with DeviceNet standards(Note) Use a special cable for DeviceNet that complies with the DeviceNet standards. |
| 消費電流 | 100 mA or less (without connected sensor amplifiers) |
| サポートされている機能 | I/O communication (Poll), Explicit message communication |
| コミュニケーション方法 | DeviceNet compliant |
| 指令遵守 | EMC Directive, RoHS Directive |
| 許容通過電流 | Wire-saving connector 2A(Note) Be sure to check that total current consumption of sensor amplifiers connected in cascade does not exceed allowable passing current. |
| 接続可能なユニット数 | Maximum of 16 units per SC-GU3-02 unit(Max. 12 units when FX-500 / LS-500 series are connected)(Max. 12 units when FX-500 / LS-500 series are connected) |
| ボーレート / 総延長距離 | 500kbps / 100m328.084 ft(thick cable) 100m328.084 ft(thin cable)250kbps / 250m820.21 ft(thick cable) 100m328.084 ft(thin cable)125kbps / 500m1640.42 ft(thick cable) 100m328.084 ft(thin cable) |
技術仕様と性能データ
設置・操作ガイド