HC-M-02-MOD-BU - HC-M-02-MOD-BU 1679359 PHOENIX CONTACT HEAVYCON contact insert module, female, 2-pos., axial screw connection
在庫あり 注目商品

HC-M-02-MOD-BU

HC-M-02-MOD-BU 1679359 PHOENIX CONTACT HEAVYCON contact insert module, female, 2-pos., axial screw connection

$0.00米ドル
4412 在庫あり
主な仕様
:Note regarding axial connection technology:Only for stranded wires. The conductor cross sections stated refer to the geometric cross section of the cable used.Use of cables with a geometric cross section very different from that of the cable's nominal cross section should be checked before use.The wiring space of the axial screw method is designed for fine strand cables according to VDE 0295 class 5. Deviating cable structures (e.g. class 6 cables) should be checked before use.ConnectionBefore starting to connect, ensure that the tapered screw is turned back all the way (chamber is open). The cables must not be twisted. The cores should be slid to the limit stop in the contact chamber (until insulation touches contact). Hold cores in position and use socket wrench to tighten. The used core end should be cut off before connecting again. The connection screw may only be retightened once to prevent the strands from breaking. To prevent damage to the contact, the core / cable should be mechanically intercepted at an appropriate distance from the connection point (e.g. by using a plate cutout). DIN VDE 0100-520:2003-06 contains information on how to do this correctly.
幅:34.2 mm
身長:40.6 mm
長さ:14.6 mm
サプライヤー情報
製品: 0
通常、2〜3営業日以内に出荷します
品質保証済み
高速配送
テクニカルサポート

技術仕様

パラメータ価値
Note regarding axial connection technology:Only for stranded wires. The conductor cross sections stated refer to the geometric cross section of the cable used.Use of cables with a geometric cross section very different from that of the cable's nominal cross section should be checked before use.The wiring space of the axial screw method is designed for fine strand cables according to VDE 0295 class 5. Deviating cable structures (e.g. class 6 cables) should be checked before use.ConnectionBefore starting to connect, ensure that the tapered screw is turned back all the way (chamber is open). The cables must not be twisted. The cores should be slid to the limit stop in the contact chamber (until insulation touches contact). Hold cores in position and use socket wrench to tighten. The used core end should be cut off before connecting again. The connection screw may only be retightened once to prevent the strands from breaking. To prevent damage to the contact, the core / cable should be mechanically intercepted at an appropriate distance from the connection point (e.g. by using a plate cutout). DIN VDE 0100-520:2003-06 contains information on how to do this correctly.
34.2 mm
身長40.6 mm
長さ14.6 mm
シリーズHC-M-02
一般的なFor HEAVYCON housing type B6 to B48, HC-M-MHR... hinged retaining frame required
応用Power
製品タイプModular contact insert
組み立てノート- Connection of the wires using a 2 mm Allen wrench.- Housing height ≥ 52 mm.- Axial screw connection only for flexible wires.- Plug-in connections may only be operated only when there is no load/voltage.
定格電流40 A
接触材料Copper alloy
六角ソケットSW 2
連絡先番号1 - 2
締め付けトルク1.5 Nm (2.5 mm² ... 4 mm²)
接続プロファイル2
汚染度3
寸法図
ポジション数2
定格サージ電圧8 kV
過電圧カテゴリーIII
接続技術Axial screw connection
定格電圧(III/3)1000 V
モジュールスロットの数1
導体断面積2.5 mm² ... 8 mm² (The cross section specification refers to the geometric cross section of the cable used)
接触キャリア材料PC
接触面材質Ag
挿入/離脱サイクル≥ 500
接続断面積AWG12 ... 10
周囲温度(動作)-40 °C ... 125 °C
標準に準拠した接続IEC / EN
UL 94準拠の難燃性評価V0
個々の電線の被覆剥き長さ8 mm +1 mm (for 6 mm²)